Content on this page requires a newer version of Adobe Flash Player.

Get Adobe Flash player

 
 








LEUTRON Surge Arrester
LEUTRON PowerPro-BCD-Tr
  • SPD based on isolating spark gap technology
  • Lightning impulse current 25 kA (10/350 micro sec)
  • Follow current extinguishing capability up to 17.5 kA eff (50 Hz)
  • No blow-out vents - no need for safety distance
  • Backup fuse up to 250 A
  • Protection level < 1kV

 

Product Descriptions

PowerPro-BCD is equipped with a newly developed, gas-filled isolating spark gap (inert gas). It has been designed in accordance with E DIN VDE 0675 part 6 (issued 11/89) and part 6/A1 (issued 3/96) as well as with IEC 61643-1 and is capable of discharging short circuit current pules of < 17.5 kA eff automatically. It has a protection level of < 1 kV. These remarkable properties can be achieved by using a completely new construction element which does not need any safety devices as it is hermetically sealed. Follow-on current measurements carried out at IPH Berlin show that there are absolutely no follow-on currents in the mains in more than 70 % of the cases (at lk = 17.5 kA eff). Any follow-on current detected (at lk = 17.5 kA eff) is effectively reduced by PowerPro-BCD-Tr to a level that 35 A fuse will not be triggered.

In practical terms, this means that users of PowerPro-BCD-Tr can be sure of a high degree of availability, low risk exposure and therefore a long service life of their systems.

 

Technical Data
Application
  • Lightning SPD meeting protection categories B, C and D for lightning current equipotential bonding and equipment protection against line-induced overvoltages
  • Single-pole device
Protection category    
B+C+D (Protection Category 1)
Tested acc. to    
E DIN VDE 0675-6-11/89-A1
Nominal DC spark over voltage Uagn
[ V=]
>800
Rated voltage 50/60 Hz UN
[ V~]
230/400
Max operating voltage 50/60 Hz Ur, c
[ V~]
255
Insulation resistance Risol
[ohm]
>1010
Impulse spark-over voltage 1.2/50 µs Uas
[kV ]
<1.0
Protection level Up
[kV ]
<1.0
Response time tA
[ns]
<50
Lightning impulse current 10/350 µs Ipeak
[kA]
25
  Q
[As]
12.5
  W/R
[kJ/ohm]
160
Extinguishing current (50 Hz) capability up to  
[kA eff]
17,5 ( IEC: 3.0)
Max. permissible line resp. backup fuse    
250 A gL
Operating temperature range T
[Celcius]
-40 to 85 degree
Max. connection wire cross-sectional area  
[mm2]
50 rigid or 35 stranded
Recommended connection wire  
[mm2]
50 rigid
Recommended connection torque  
[Nm]
4.5
Housing cover / Colour    
Polycarbonate (halogen-free) /yellow
Acc. to IEC 529 (1989) protection category    
IP 20
Mounting    
35 mm rail according to EN 50 022
Potential-Free Contact    
PowerPro-BCD-Tr/25kA/Pk

|    Home  |    Company Info    |   Business Partner   |  Products   |  Contact Us   |
Copyright © 2009-2010 MIKIMOTO.CO.,LTD. All Rights Reserved. Website by Maximus.com.my
Japan Site