| Technical Data |
| Application |
- Lightning SPD meeting protection categories B, C and D for lightning current equipotential bonding and equipment protection against line-induced overvoltages
- Single-pole device
|
| Protection category |
|
|
B+C+D (Protection Category 1)
|
| Tested acc. to |
|
|
E DIN VDE 0675-6-11/89-A1
|
| Nominal DC spark over voltage |
Uagn |
[ V=]
|
>800
|
| Rated voltage 50/60 Hz |
UN |
[ V~]
|
230/400
|
| Max operating voltage 50/60 Hz |
Ur, c |
[ V~]
|
255
|
| Insulation resistance |
Risol |
[ohm]
|
>1010
|
| Impulse spark-over voltage 1.2/50 µs |
Uas |
[kV ]
|
<1.0
|
| Protection level |
Up |
[kV ]
|
<1.0
|
| Response time |
tA |
[ns]
|
<50
|
| Lightning impulse current 10/350 µs |
Ipeak |
[kA]
|
25
|
| |
Q |
[As]
|
12.5
|
| |
W/R |
[kJ/ohm]
|
160
|
| Extinguishing current (50 Hz) capability up to |
|
[kA eff]
|
17,5 ( IEC: 3.0)
|
| Max. permissible line resp. backup fuse |
|
|
250 A gL
|
| Operating temperature range |
T |
[Celcius]
|
-40 to 85 degree
|
| Max. connection wire cross-sectional area |
|
[mm2]
|
50 rigid or 35 stranded
|
| Recommended connection wire |
|
[mm2]
|
50 rigid
|
| Recommended connection torque |
|
[Nm]
|
4.5
|
| Housing cover / Colour |
|
|
Polycarbonate (halogen-free) /yellow
|
| Acc. to IEC 529 (1989) protection category |
|
|
IP 20
|
| Mounting |
|
|
35 mm rail according to EN 50 022
|
| Potential-Free Contact |
|
|
PowerPro-BCD-Tr/25kA/Pk
|